Por favor, use este identificador para citar o enlazar este ítem: https://repositorio.ufu.br/handle/123456789/29338
Tipo de documento: Tese
Tipo de acceso: Acesso Aberto
Título: Análise da geração assíncrona distribuída utilizando gás metano proveniente da suinocultura
Título (s) alternativo (s): Analysis of distributed asynchronous generation using methane gas from swine breeding
Autor: Silva, Eudinei de Oliveira
Primer orientador: Guimarães, Geraldo Caixeta
Primer miembro de la banca: Moraes, Adélio José de
Segundo miembro de la banca: Martins Neto, Luciano
Tercer miembro de la banca: Silva, Fernando Bento
Cuarto miembro de la banca: Silva, Rui Vagner Rodrigues da
Resumen: A Resolução Normativa 482/2012 da Agência Nacional de Energia Elétrica (ANEEL) permite a conexão de geradores ao sistema de distribuição. A geração distribuída possui como característica principal possuir pequenas unidades geradoras conectadas diretamente à rede de distribuição. Esse tipo de geração com fontes alternativas está crescendo em número e em potência, principalmente pelo forte apelo ambiental. No entanto, os críticos da geração distribuída apontam problemas técnicos, operacionais, de qualidade e principalmente de segurança (como a alimentação acidental da rede de distribuição). O objetivo da pesquisa é estudar o comportamento da máquina assíncrona na geração distribuída trabalhando em condições reais ( com presença de harmônicos e desequilíbrio de tensão e corrente), operando conectada à rede principal ou em condição ilhada. Simplicidade operacional, menor custo de implantação e manutenção e, principalmente, segurança são aspectos relevantes considerados na pesquisa. Neste caso, o combustível primário da máquina é o gás metano proveniente da suinocultura. O gerador de indução opera na condição de regime permanente, linear, não- senoidal e desequilibrada, empregando um banco de capacitores para o fornecimento da potência reativa necessária. Isto se justifica para evitar a necessidade de importar reativos da rede o que seria economicamente inviável. Para validar a proposta, são realizados ensaios experimentais e simulações computacionais. Os resultados práticos são coletados de uma instalação elétrica real, usando equipamentos comerciais que atendem aos padrões de uma empresa de energia elétrica. Os resultados virtuais vêm da representação do sistema elétrico usando o Matlab/Simulink®. Ao final, conclui-se que ambos os tipos de resultados mostraram boa concordância.
Abstract: The normative resolution 482/2012 of the National Electric Energy Agency (ANEEL) allows the connection of generators to the distribution system. Distributed generation has as main feature the use of small generating units connected directly to the distribution network. This type of generation with alternative sources is growing in number and power, mainly by strong environmental appeal. However, critics of the distributed generation point technical, operational, quality issues and notably those concerned to security (such as accidental supply of the distribution network). The research goal is to study the behavior of the asynchronous machine in distributed generation working in real conditions (with presence of harmonics and voltage and current unbalances), connected to the main grid or on islanding operation. Operational simplicity, lower cost of deployment and maintenance, and especially the safety are relevant aspects considered in the research. In this case, the primary machine fuel is the methane gas from pig farming. The induction generator operates on a steady-state, linear, non-sinusoidal and unbalanced condition, employing a capacitor bank to supply the necessary reactive power. This is justified to avoid the need to import such power from the network, which would be economically unfeasible. To validate the proposal experimental tests and computer simulations are performed. Practical results are collected from a real electrical installation, using commercial equipment that meet the standards of an electric power utility. Virtual results come from the electric system representation using the Matlab/Simulink®. Finally, it is concluded that both types of results have showed good agreement.
Palabras clave: Gerador de indução
Geração distribuída
Desequilíbrio
Harmônicos
Ilhamento
Simulação
Induction generator
Distributed generation
Unbalance
Harmonics
Islanding
Simulation
Matlab/Simulink®
Área (s) del CNPq: CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
Idioma: por
País: Brasil
Editora: Universidade Federal de Uberlândia
Programa: Programa de Pós-graduação em Engenharia Elétrica
Cita: SILVA, Eudinei de Oliveira. Análise da geração assíncrona distribuída utilizando gás metano proveniente da suinocultura. 2020. 141 f. Tese (Doutorado em Engenharia Elétrica) - Universidade Federal de Uberlândia, Uberlândia, 2020. DOI http://dx.doi.org/10.14393/ufu.te.2019.2392
Identificador del documento: http://dx.doi.org/10.14393/ufu.te.2019.2392
URI: https://repositorio.ufu.br/handle/123456789/29338
Fecha de defensa: 24-abr-2020
Aparece en las colecciones:TESE - Engenharia Elétrica

Ficheros en este ítem:
Fichero Descripción TamañoFormato 
AnaliseGeracaoAssincrona.pdfTese5.89 MBAdobe PDFVista previa
Visualizar/Abrir


Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.