Please use this identifier to cite or link to this item: https://repositorio.ufu.br/handle/123456789/14283
metadata.dc.type: Tese
metadata.dc.rights: Acesso Aberto
Title: Um estudo das alterações dos parâmetros de transformadores oriundas de deformações nos enrolamentos: uma contribuição para o diagnóstico de vida útil
Other Titles: A study of transformer parameter changes caused by deformations in windings: a contribution to lifetime diagnosis
metadata.dc.creator: Saraiva, Elise
metadata.dc.contributor.advisor1: Guimarães, Geraldo Caixeta
metadata.dc.contributor.advisor-co1: Chaves, Marcelo Lynce Ribeiro
metadata.dc.contributor.referee1: Camacho, Jose Roberto
metadata.dc.contributor.referee2: Neves, Washington Luiz Araujo
metadata.dc.contributor.referee3: Paula, Helder de
metadata.dc.description.resumo: Esta tese tem como objetivo estudar as alterações que possam ocorrer nos parâmetros de transformador quando algum tipo de deformação incidir em seus enrolamentos. Para a verificação de tais efeitos, optou-se por analisar possíveis variações em parâmetros elétricos, magnéticos e mecânicos as quais podem indicar um decaimento na vida útil de tal equipamento. Para o desenvolvimento de tal estudo optou-se por utilizar duas ferramentas computacionais para modelar o transformador: o software ATP (Alternative Transient Program) e o programa FLUX em sua versão 3D, o qual emprega o método de elementos finitos. Deformações serão aplicadas nos modelos e análises realizadas para a verificação dos parâmetros supracitados. De posse de tais análises e de técnicas já utilizadas para a detecção de deformações mecânicas nos enrolamentos de transformadores, será apresentada uma metodologia computacional para a realização de tal diagnóstico, antes que este tipo de falha possa retirar o transformador de operação.
Abstract: This thesis aims to study the changes that may occur in transformer parameters when any type of deformation is caused in its windings. To verify such effects, it will be analyzed possible variations in electrical, magnetic and mechanical parameters, which may indicate a lifetime decay of such equipment. To conduct this work, it will be used two computational tools for transformer modeling: ATP (Alternative Transient Program) and FLUX 3D which employs the finite element method. Some deformations are then applied in the transformer windings in order to verify the aforementioned parameters. Therefore, with such studies and techniques able to detect mechanical deformations in transformer windings, a computer methodology is developed for carrying out a diagnosis before such kind of failure removes the transformer from operation.
Keywords: Transformadores
Metodologia computacional
Método dos elementos finitos
ATP
Deformações nos enrolamentos
Transformers
Computer methodology
Finite element method
Winding deformations
Transformadores elétricos
metadata.dc.subject.cnpq: CNPQ::ENGENHARIAS::ENGENHARIA ELETRICA
metadata.dc.language: por
metadata.dc.publisher.country: BR
Publisher: Universidade Federal de Uberlândia
metadata.dc.publisher.initials: UFU
metadata.dc.publisher.department: Engenharias
metadata.dc.publisher.program: Programa de Pós-graduação em Engenharia Elétrica
Citation: SARAIVA, Elise. A study of transformer parameter changes caused by deformations in windings: a contribution to lifetime diagnosis. 2011. 220 f. Tese (Doutorado em Engenharias) - Universidade Federal de Uberlândia, Uberlândia, 2011.
URI: https://repositorio.ufu.br/handle/123456789/14283
Issue Date: 19-Sep-2011
Appears in Collections:TESE - Engenharia Elétrica

Files in This Item:
File Description SizeFormat 
t.pdf4.82 MBAdobe PDFView/Open


Items in DSpace are protected by copyright, with all rights reserved, unless otherwise indicated.